| Parameter | Standard Range |
|---|---|
| Rated capacity | 6.3–100 MVA (typical: 10/16/20/31.5/40/50/63/80/100) |
| Primary voltage | 66 kV (max 72.5 kV) |
| Secondary voltage | 10, 11, 35 kV / custom |
| Frequency | 50 Hz or 60 Hz |
| Phase | 3-phase |
| Vector group | YNd11, YNd1 (custom) |
| Impedance | 9% – 13% (per spec) |
| Cooling method | ONAN / ONAF |
| Tap changer | On-load (OLTC) ±8×1.25% |
| Insulation level | LI325AC140 (66kV) |
| Temperature rise | 65K (oil); 65K (winding) |
| No-load loss | Per IEC 60076 / customer spec |
| Load loss | Per IEC 60076 / customer spec |
| Noise level | ≤65 dB (per IEC 60076-10) |
| Protection level | IP00 indoor; IP54 outdoor |
| Applicable standards | IEC 60076, IEEE C57.12.00 |
| Ambient temperature | -25°C to +40°C |
| Altitude | ≤1000m (derating above) |
| Accessories | OLTC, Buchholz, temp gauges, pressure relief, control cubicle |
Product Advantages
Verifiable benefits — not empty claims. Here’s exactly what you get when you choose JINXING.
Full Routine Test
IEC 60076-1 routine tests on every unit.
Fast Response
48h standard quote; 3–5 days custom.
English Docs
Complete documentation in English.
Witness FAT
Third-party witness testing available.
OEM Support
Custom branding and private label.
OLTC Standard
On-load tap changer included as standard.

Applications
Where this transformer is used — connecting the product to real-world industry applications.
Sub-transmission
66kV regional distribution substations.
Industrial
Factory main supply — 66/10kV step-down.
City Substation
Urban distribution — 66kV to 10kV.
Renewable
Solar/wind farm collection — 66kV.
Quality Proof — 9-Step Manufacturing Process
Every transformer passes through 9 quality-controlled stages, from raw material to shipping. Full traceability with documentation at every step.

Material Inspection
Raw material verification — core steel, copper, oil, accessories checked against certificates before production.
Core Cutting
CNC step-lap core cutting for low-loss grain-oriented silicon steel. Core loss measured before assembly.
Winding
Controlled winding tension, turn-count verification, and insulation paper application for each coil.
Assembly
Core-coil assembly with dimensional checks for fit, clearance, and clamping force.
Vacuum Drying
High-vacuum drying ovens remove moisture from insulation before oil impregnation.
Oil Filling
Filtered insulating oil with breakdown voltage >70kV/2.5mm and moisture <10ppm.
Final Testing
Full routine test per IEC 60076-1 — insulation, resistance, ratio, losses, withstand.
Packing
Sea-worthy export packing with shock-fixed crating for ocean shipping.
Shipping
On-time delivery with documentation — test reports, drawings, manuals in English.
Need a Custom Transformer Solution?
Our engineering team can assess non-standard voltage, capacity, impedance, or environmental conditions — and deliver a full proposal within 48 hours.